FEATURE
-The KAL760 is an addressable single input unit for KSA700/FP1500 fire systems. It provides a remote input to the fire system loop that is constantly monitored for open and short circuit conditions. The input may be activated by closing a potential free contact.
-The KAL760 may be used to monitor both pre-alarm and alarm states of any potential free contact and report this status to the fire control panel e.g. the monitoring of pressure equipment, aspiration systems, flow switches, doors, etc.
-EN54:18 and CPD certified
-Surface mount
-Easy addressing
-External or loop powered
-Local alarm and communications indication
-Normally open switch supervision
-Part of a family of I/O modules consisting of:
-Conventional zone monitors
-Digital input modules
-Extinguishing control modules
-Loop Isolators
-Manual call points
-Relay and supervised output units
-Fire door controllers
SPECIFICATION
MODEL
|
KAL760
|
Supply Voltage
|
Supply Voltage
|
22 ~ 38VDC
|
Current Consumption (External Power)
|
Quiescent @ 24 V
|
110µA
|
Quiescent @ 35 V
|
135µA
|
Alarm
|
< 10mA
|
Aux. 24 VDC Quiescent
|
200µA
|
Aux. 24 VDC Alarm
|
< 50mA
|
Current Consumption (Loop Power)
|
Standby
|
750µA
|
Alarm
|
< 3.6mA
|
Resistors
|
End Of Line Resistor
|
270KOhm
|
Alarm
|
100KOhm
|
Pre-alarm
|
39KOhm
|
Environmental
|
Storage Temperature
|
-10°C ~ +70°C
|
Operating Temperature
|
-10°C ~ +50°C
|
Relative Humidity (non-cond.)
|
10~95 %
|
IP Rating
|
IP55
|
Physical
|
Dimensions (L x W x H)
|
150 x 110 x 70mm
|
Colour
|
Grey
|
Weight
|
370g
|