FEATURE
-The KL735A is an addressable multi-criteria detector. It acts as a dual device (optical and heat detector) and has the ability to report fire alarms both as a standard smoke detector, or as a temperature sensor (Class A2R) – fixed temperature at 60°C with a rate-of-rise trigger should the temperature in the environment change faster than the pre-set limits
-The KL700A Series uses a microprocessor for measurement and communication. An enhanced protocol ensures the overall integrity and error free operation of the fire system, without compromising speed. All sensors are compatible with a standard base that makes them easily interchangeable and that supports the connection of a remote indicator
-Remote signalling capabilities
-Fixed and Rate-of-Rise heat detectors
-Easy soft addressing (1 ~ 125)
-SMD technology
-Reliable communication protocol
-Full diagnostic self testing
-Full range: Ionisation, Optical and Heat and Duel sensors (optical/heat)
-Full range of supporting I/O units and accessories
-EN54 Approved
SPECIFICATION
MODEL
|
KL735A
|
Operating Voltage
|
22 ~ 38VDC
|
Current consumption
|
Quiescent / 38VDC
|
350µA
|
In Alarm
|
< 5mA
|
Alarm Indication (dual LED)
|
Red
|
Remote Alarm Output
|
Available
|
Storage Temperature
|
-10°C ~ +70°C
|
Operating Temperature
|
-10°C ~ +70°C
|
Humidity (non condensing)
|
95%
|
IP Rating
|
IP42
|
Radioactive Source
|
NA
|
Dimensions (H x Ø)
|
51 x 99mm
|
Coverage
|
60 ~ 80m²
|