FEATURE
-Honeywell's feature-rich TS300 was engineered to meet the demands of a wide range of applications. From florists and butchers to pet shops, computer centers and residences, the TS300 provides uncompromising performance. Unique features such as simultaneous use of local and remote temperature probes, programmable hysteresis and audible alarm with silence timeout, illustrate the sensor’s flexibility in installation, programming and operation.
Flexibility
-The TS300 allows the end-user to independently program local and remote temperature probes in accordance with varying environmental requirements.
Audible Alarm with Silence Timeout
-The TS300 is equipped with an audible alarm which sounds once the temperature at an enabled sensor varies outside of it’s defined limits. The TS300 allows users to designate a “time-out” time. With the touch of a button, users may silence a sounding alarm for a period of time.
Versatility
-The TS300 is a dual temperature sensor that has the capacity to simultaneously monitor both local and remote temperature probes.
Programmable Alarm Delay
-Designed to reduce the occurrence of nuisance alarms during temporary conditions this feature allows the user to delay the sounding of the alarm for a designated period of time. Routine task, which may cause the temperature to rise above or fall below the programmed alarm point, may be completed without generating an alarm.
Alarm Memory
-Easy way to check function and detection area.
Programmable Hysteresis
-Temporary conditions often influence the gradual rise and fall of temperatures around the alarm point. Under such conditions, conventional sensors generate multiple alarms and restore messages. With the Programmable Hysteresis feature, an alarm is generated only the first time the temperature reaches the alarm point. As long as the temperature fluctuates within the “Hysteresis Range”, no subsequent alarms will be transmitted until the environment has reached the predetermined restore temperature.
SPECIFICATION
|
MODEL
|
TS300
|
|
Temperature Range/Accuracy
|
8.0V ~ 15VDC
|
|
Local Sensor
|
0°C ~ +60°C, +/-1.7°C
|
|
Remote Probe (T280R)
|
-40°C ~ +60°C, +/-2.2°C
|
|
Hi And Low Limits
|
Minimum span between, 2.2°C
|
|
Input Voltage
|
7 ~ 16VDC
|
|
Input Current
|
25mA (max.)
|
|
Case Dimensions
|
10.2 x 6.6 x 2.3cm
|
|
Alarm Delay
|
0~255 minutes in 1 minute increments
|
|
Alarm Output Type
|
2x, Form A reed relays
|
|
Alarm Output Resistance
|
25 ohms maximum
|
|
Alarm Output Rating
|
50mA/30VDC maximum
|
|
Audible Alarm
|
4KHz, 75dB@10cm pulsed 750 ms on/off
|
|
Audible Alarm Silencing
|
0~255 minutes in 1 minute increments
|